Medium-voltage voltage transformers
For rated operating voltages of 6, 6.3, 10, 15 and 20 kV, for installation in indoor switchgear. Unearthed (two-pole) and earthed (single-pole) versions.
Construction
The transformers have a laminated core of electrical steel. The LV winding is wound on the core and the HV primary winding, made of separate sections, is fitted over it. The active part is cast in epoxy resin compound of insulation class F. The transformers meet the requirements of BDS EN 60044-2.
Operating conditions
- Ambient temperature−25 to +40 °C
- Altitudeup to 1000 m
- Climatenormal and tropical climate versions
| Type | Rated primary voltage Upn, kV | Ratio Upn / Usn, kV | Output, rated / limit Pn / Ppr, VA | Accuracy class | Mass, kg |
|---|---|---|---|---|---|
| NK-7.2 | 6 | 6 / 0.1 | 100 / 400 | 0.5 | 27 |
| NK-7.2 | 6.3 | 6.3 / 0.1 | 100 / 400 | 0.5 | 27 |
| NK-I-7.2 | 6 : √3 | 6:√3 / 0.1:√3 / 0.1:3 | 50 / 200 | 0.5 | 26.5 |
| NK-I-7.2 | 6.3 : √3 | 6:√3 / 0.1:√3 / 0.1:3 | 50 / 200 | 0.5 | 26.5 |
| NK-12 | 10 | 10 / 0.1 | 100 / 500 | 0.5 | 27 |
| NK-12 | 11 | 11 / 0.1 | 100 / 500 | 0.5 | 27 |
| NK-12 | 11 | 11 / 0.11 | 80 / 500 | 0.5 | 27 |
| NK-I-12 | 10 : √3 | 10:√3 / 0.1:√3 / 0.1:3 | 50 / 300 | 0.5 | 26.5 |
| NK-I-12 | 10.5 : √3 | 10.5:√3 / 0.1:√3 / 0.1:3 | 50 / 300 | 0.5 | 26.5 |
| NK-I-12 | 11 : √3 | 11:√3 / 0.1:√3 / 0.1:3 | 50 / 300 | 0.5 | 26.5 |
| NK-I-12 | 11 : √3 | 11:√3 / 0.11:√3 / 0.11:3 | 50 / 300 | 0.5 | 26.5 |
| NK-24 | 15 | 15 / 0.1 | 120 / 750 | 0.5 | 40 |
| NK-24 | 20 | 20 / 0.1 | 120 / 750 | 0.5 | 40 |
| NK-I-24 | 15 : √3 | 15:√3 / 0.1:√3 / 0.1:3 | 60 / 500 | 0.5 | 40 |
| NK-I-24 | 20 : √3 | 20:√3 / 0.1:√3 / 0.1:3 | 60 / 500 | 0.5 | 40 |
ZAVN-Dobrich AD can make these voltage transformer designs with other technical parameters (accuracy class, rated primary and secondary voltage and so on) to BDS, IEC and GOST, to the client's order.
The type-approval certificates of NK and NK-I are on the Documents page.
The other products
- Packaged transformer substations (MKTP and BKTP)7.2, 12 and 24 kV, with ABB, Siemens and Schneider apparatus
- Switchgear assemblieswith minimum-oil, SF₆ and vacuum circuit breakers, 7.2, 12, 24 kV
- Low-voltage switchboards0.4 kV, to BDS EN 60439
- Indoor current transformers0.5 kV, up to 3000 A
- Current transformersfor 10, 20 and 35 kV, from 10 to 4000 A
- Epoxy insulators0.66, 7.2, 12 and 24 kV, and epoxy parts to the client's drawings
- High-power fuses type VPm7.2, 12 and 24 kV, current-limiting
- Retrofit and rehabilitation of MV switchgear breakersreplacing minimum-oil breakers with vacuum and SF₆ ones